Fan selection
THGT-JFU — Axial smoke extract jet fan
THGT-JFU/2/4-450 BC · 50Hz
PN-SP-THGT-JFU-2-4-450-BC-50HZ
Operating frequency
Emergency smoke extraction
Series executions · 120 minutes
Normal operating temperature
−20…+40 °C
Everyday operation
Airflow direction
Unidirectional
Air movement
Motor modes
Two speeds
Manufacturer data
Specify the temperature execution when ordering. The F rating describes emergency smoke extraction.
Thrust and operating modes
THGT-JFU/2/4-450 BC · 50Hz
| Technical parameter | 2 860 rpm | 1 425 rpm |
|---|---|---|
| Thrust | 88 N | 23 N |
| Flow | 12 600 m³/h | 6 200 m³/h |
| Motor power | 2.2 kW | 0.5 kW |
| Current | 4.6 A | 1.5 A |
| Sound pressure level | 61 dB(A) | 43 dB(A) |
The diagram shows published catalogue operating modes. Thrust is in newtons; this is not a continuous P–Q curve.

Series illustration
Photos and specifications
Soler & Palau jet fan for inducing air movement in car parks and large spaces. Galvanized steel casing, external electrical connection and protection guard. Read more →
Selected model specifications
THGT-JFU/2/4-450 BC · 50Hz · PN-SP-THGT-JFU-2-4-450-BC-50HZ
| Manufacturer | Soler & Palau |
|---|---|
| Power | 2.2 / 0.5 kW |
| Speed | 2860 / 1425 rpm |
| Flow | 12600 / 6200 m³/h |
| Thrust | 88 / 23 N |
| Voltage | 400 V |
| Frequency | 50 Hz |
| Current | 4.6 / 1.5 A |
| Number of phases | 3 |
| Insulation class | H |
| Sound pressure level | 61 / 43 dB(A) |
| Weight | 89 kg |
| Airflow direction | Unidirectional |
| Normal operating temperature | −20…+40 °C |
| Motor protection class | IP55 |
| Series emergency executions | F200-120 / F300-120 |
| Emergency operating duration | 120 min |
| Standard | EN 12101-3 |
| Number of poles | 2/4 |
| Air velocity | 22 / 11 m/s |
Price
on request
Send an inquiry to receive prices and delivery terms within 1–2 days.
Send an inquiryContact us- Official dealer for 20+ brands
- Delivery in Georgia
- 20+ years of experience
Models and technical data
Selected model: THGT-JFU/2/4-450 BC · 50Hz50 Hz
- Flow
- 12600 / 6200 m³/h
- Pressure
- —
- Power
- 2.2 / 0.5 kW
- Speed
- 2860 / 1425 rpm
Select a model or its data in the table.
16 / 16 Model · 50 Hz
| Model | Power (kW) | Speed (rpm) | Flow (m³/h) | Thrust (N) | Voltage (V) | Frequency (Hz) |
|---|---|---|---|---|---|---|
| 2.2 / 0.5 | 2860 / 1425 | 12600 / 6200 | 88 / 23 | 400 | 50 | |
| 2.2 / 0.5 | 2860 / 1425 | 12600 / 6200 | 88 / 23 | 400 | 50 | |
| 4.4 / 1.1 | 2890 / 1440 | 17550 / 8900 | 139 / 38 | 400 | 50 | |
| 4.4 / 1.1 | 2890 / 1440 | 17550 / 8900 | 139 / 38 | 400 | 50 | |
| 8 / 2 | 2920 / 1460 | 25500 / 12850 | 233 / 62 | 400 | 50 | |
| 8 / 2 | 2920 / 1460 | 25500 / 12850 | 233 / 62 | 400 | 50 | |
| 16 / 4 | 2950 / 1470 | 36400 / 17950 | 359 / 96 | 400 | 50 | |
| 16 / 4 | 2950 / 1470 | 36400 / 17950 | 359 / 96 | 400 | 50 | |
| 2.2 | 2880 | 12600 | 88 | 400 | 50 | |
| 2.2 | 2880 | 12600 | 88 | 400 | 50 | |
| 4 | 2900 | 17550 | 139 | 400 | 50 | |
| 4 | 2900 | 17550 | 139 | 400 | 50 | |
| 7.5 | 2930 | 25500 | 233 | 400 | 50 | |
| 7.5 | 2930 | 25500 | 233 | 400 | 50 | |
| 15 | 2945 | 36400 | 359 | 400 | 50 | |
| 15 | 2945 | 36400 | 359 | 400 | 50 |
Scroll sideways or down to view the full table.
About this product
Description
Jet fans
THGT-JFU — Axial smoke extract jet fan
Selected model: THGT-JFU/2/4-450 BC · 50Hz
SKU PN-SP-THGT-JFU-2-4-450-BC-50HZ
Series emergency executions: F200-120 / F300-120 · 120 min · Normal operating temperature: −20…+40 °C · Specify the temperature execution when ordering.

Selected model specifications
- Manufacturer
- Soler & Palau
- Power
- 2.2 / 0.5 kW
- Speed
- 2860 / 1425 rpm
- Flow
- 12600 / 6200 m³/h
- Thrust
- 88 / 23 N
- Voltage
- 400 V
- Frequency
- 50 Hz
- Current
- 4.6 / 1.5 A
- Number of phases
- 3
- Insulation class
- H
- Sound pressure level
- 61 / 43 dB(A)
- Weight
- 89 kg
- Airflow direction
- Unidirectional
- Normal operating temperature
- −20…+40 °C
- Motor protection class
- IP55
- Series emergency executions
- F200-120 / F300-120
- Emergency operating duration
- 120 min
- Standard
- EN 12101-3
- Number of poles
- 2/4
- Air velocity
- 22 / 11 m/s
- Catalogue base model
- THGT-JFU/2/4-450 BC
- Series
- THGT-JFU
- Number of operating modes
- 2
- Electrical connection
- With terminal box
- A
- 310 mm
- B
- 556 mm
- C/C
- 308 mm
- C/I
- 360 mm
- D
- 536 mm
- E
- 636 mm
- H
- 555 mm
- L
- 1754 mm
- L1
- 1769 mm
Power and current may depend on the motor used. Sound pressure is measured at 3 m. Confirm the full factory execution on the nameplate.
Thrust and operating modes
THGT-JFU/2/4-450 BC · 50Hz
| Technical parameter | 2 860 rpm | 1 425 rpm |
|---|---|---|
| Thrust | 88 N | 23 N |
| Flow | 12 600 m³/h | 6 200 m³/h |
| Motor power | 2.2 kW | 0.5 kW |
| Current | 4.6 A | 1.5 A |
| Sound pressure level | 61 dB(A) | 43 dB(A) |
The diagram shows published catalogue operating modes. Thrust is in newtons; this is not a continuous P–Q curve.