Fan selection

TJHU — Unidirectional smoke extract jet fan

TJHU/2-315-BC · 50Hz

PN-SP-TJHU-2-315-BC-50HZ

Operating frequency

Emergency smoke extraction

F200-120F300-120F400-120

Series executions · 120 minutes

Normal operating temperature

−20…+40 °C

Everyday operation

Airflow direction

Unidirectional

Air movement

Motor modes

Single speed

Manufacturer data

Specify the temperature execution when ordering. The F rating describes emergency smoke extraction.

Thrust and operating modes

TJHU/2-315-BC · 50Hz

Thrust (N)014.37528.752 790 rpm · 25 N · 4 600 m³/h25 N2 790 rpm
Technical parameter2 790 rpm
Thrust25 N
Flow4 600 m³/h
Motor power0.75 kW
Current1.6 A
Sound pressure level62 dB(A)

The diagram shows published catalogue operating modes. Thrust is in newtons; this is not a continuous P–Q curve.

TJHU — Unidirectional smoke extract jet fan – series illustration

Series illustration

Photos and specifications

Soler & Palau jet fan for inducing air movement in car parks and large spaces. Galvanized steel casing, external electrical connection and protection guard. Read more →

Selected model specifications

TJHU/2-315-BC · 50Hz · PN-SP-TJHU-2-315-BC-50HZ

ManufacturerSoler & Palau
Power0.75 kW
Speed2790 rpm
Flow4600 m³/h
Thrust25 N
Voltage380–415 V
Frequency50 Hz
Current1.6 A
Number of phases3
Insulation classH / F
Sound pressure level62 dB(A)
Weight56 kg
Airflow directionUnidirectional
Normal operating temperature−20…+40 °C
Motor protection classIP55
Series emergency executionsF200-120 / F300-120 / F400-120
Emergency operating duration120 min
StandardEN 12101-3
Number of poles2
Air velocity16 m/s

Price

on request

Send an inquiry to receive prices and delivery terms within 1–2 days.

Send an inquiryContact us
  • Official dealer for 20+ brands
  • Delivery in Georgia
  • 20+ years of experience
Operating frequency

Models and technical data

Selected model: TJHU/2-315-BC · 50Hz50 Hz

Flow
4600 m³/h
Pressure
—
Power
0.75 kW
Speed
2790 rpm

Select a model or its data in the table.

6 / 6 Model · 50 Hz

ModelPower (kW)Speed (rpm)Flow (m³/h)Thrust (N)Voltage (V)Frequency (Hz)
0.752790460025380–41550
1.12810680043380–41550
1.52870970068380–41550
0.8 / 0.22820 / 14004600 / —25 / —380–41550
1.1 / 0.252810 / 13906800 / —43 / —380–41550
1.5 / 0.372900 / 14359700 / —68 / —380–41550

Scroll sideways or down to view the full table.

About this product

Description

Soler & Palau jet fan for inducing air movement in car parks and large spaces. Galvanized steel casing, external electrical connection and protection guard. The model table contains manufacturer catalogue ratings; thrust is stated in newtons. For ventilation and one-off emergency smoke extraction. Series executions to EN 12101-3: F200-120 / F300-120 / F400-120, corresponding to 200 °C / 300 °C / 400 °C for 120 minutes in the respective execution. Normal operating range: −20…+40 °C. The catalogue base model code does not fix the temperature execution; specify it when ordering. Two circular attenuators, aluminium-alloy impeller and standard inlet/outlet guards. Single-speed 2-pole and two-speed 2/4-pole Dahlander motors are available.