CDL 3-4 – Vertical pump

CDL 3-4 – Vertical pump

0.37 kW (0.5 HP) · Hmax 25 m · Qmax 4 t/h (67 l/min) · DN 25 · 4 stages · AISI 304

Technical specifications

Select a value to find pumps with the same specification

Pump typeMultistage
Maximum flow (Qmax)4 t/h · 67 l/min
Maximum head (Hmax)25 m
Nominal flow3 t/h · 50 l/min
Nominal head19 m
Power0.37 kW · 0.5 HP
Speed2900 rpm
Protection classIP55
Inlet (suction)1" (25 mm)
Outlet (discharge)1" (25 mm)
Maximum fluid temperature120 °C
Casing materialCast iron
Impeller materialStainless steel
Number of stages4
Insulation classF
Frequency50 Hz
SKU CDL-3-4

Price

on request

Send an inquiry to receive prices and delivery terms within 1–2 days.

Send an inquiryContact us
  • Official dealer for 20+ brands
  • Delivery in Georgia
  • 20+ years of experience

Series comparison

The entire series in one table

23 Model in one family, with head at each flow. The model you are viewing is highlighted in dark blue.

CDL 3

Nominal 3 t/h · 50 l/minThis family
CDL 3 Family performance comparison
Modelt/h →l/min →Curve1.2201.423.31.626.71.830233.32.4402.846.73503.253.33.558.33.660466.7
CDL 3-20.37 kWVoltage not confirmed12.51211.5111110.51098776
CDL 3-30.37 kWVoltage not confirmed191918.51817.516.515141312119
CDL 3-4Current0.37 kWVoltage not confirmed252524242321.5201918161512
CDL 3-50.37 kWVoltage not confirmed313130302927252322201916
CDL 3-60.55 kWVoltage not confirmed363635353432302827242319
CDL 3-70.55 kWVoltage not confirmed434241403937343231282722
CDL 3-80.75 kWVoltage not confirmed494847464543393735323125
CDL 3-90.75 kWVoltage not confirmed555453525148454240363528
CDL 3-100.75 kWVoltage not confirmed616059585754504745413931
CDL 3-111.1 kWVoltage not confirmed676664636158545149444234
CDL 3-121.1 kWVoltage not confirmed737270696763585552474537
CDL 3-131.1 kWVoltage not confirmed787776757369646057514940
CDL 3-151.1 kWVoltage not confirmed908988868479736966595746
CDL 3-171.5 kWVoltage not confirmed103102100989690837975676452
CDL 3-191.5 kWVoltage not confirmed115114112110107100928883757258
CDL 3-212.2 kWVoltage not confirmed1281261241221191121029891827964
CDL 3-232.2 kWVoltage not confirmed140138135133130122112107100908670
CDL 3-252.2 kWVoltage not confirmed151149147144141131122116109989476
CDL 3-272.2 kWVoltage not confirmed16416215915615214313212411710510182
CDL 3-292.2 kWVoltage not confirmed17517317016716315314213312611310988
CDL 3-313 kWVoltage not confirmed18718518217917516515314213512111694
CDL 3-333 kWVoltage not confirmed199197194191187176163151145130125100
CDL 3-363 kWVoltage not confirmed218215212208204192178168159143137109
Table 1. CDL 3 – columns show flow in t/h, with l/min below; cells show head in metres.

Source: manufacturer's technical sheet.Values are for reference. In a real system, pipe diameter, length and bends reduce the available head.

Technical sheet

Model CDL 3-4

Performance curve

A pump has a performance curve rather than a single flow and head. Qmax and Hmax are at opposite ends and never occur together: at maximum head, flow is zero; at maximum flow, head is zero. Actual operation lies between these extremes.

Hmax 25 mQmax4 t/h66.7 l/min0102030t/h012345l/min020406080Head, mFlow
Maximum head
25m

1.2 t/h
20 l/minat

Maximum flow
4t/h

66.7 l/min· at 12 m

Midpoint
20m

2.8 t/h
46.7 l/minat

Chart 1. Head (m) against flow (t/h, l/min), CDL 3-4. Blue points show the manufacturer's measured values. Move the pointer near the curve, or touch it on a phone, to read the head and flow at any point.

Measured values

Performance table
t/h
l/min
Head, m

Select a number in the table to see the corresponding point.

CDL 3-4 – Vertical pump · PN.GE