FE PETRO MLD-HC — high-capacity line leak detector – series illustration

Series illustration

FE PETRO MLD-HC — high-capacity line leak detector

FE PETRO MLD-HC is a mechanical detector for high-capacity fuel lines. Under the specified conditions it detects leaks of 3 gph (11. Read more →

Model code (SKU)PN-FF-401315902
Model
401315902
Factory order code
401315902
brands
FE PETRO / Franklin Electric
Leak detection
3 gph / 11.4 L/h @ 10 psi
Application
Gasoline

Price

on request

Send an inquiry to receive prices and delivery terms within 1–2 days.

Send an inquiryContact us
  • Official dealer for 20+ brands
  • Delivery in Georgia
  • 20+ years of experience

Select a model by clicking its data in the table.

Compare models

Model

Construction, operation and model selection

Detailed description and use

System application and installation

Installed, grouped and component views

MLD-HC adapter and tank return
High-capacity pump in an installation

MLD-HC adapter and tank return

MLD-HC/HCD mounts into the line using its appropriate adapter tee. The top vent connects to the tank port while the detector monitors the pressurized delivery line. Check the drawing’s horizontal and vertical clearances against the actual sump. Installation includes an initial line-integrity test followed by the manual’s detector functional test.

Air removal and leak testing

Trapped air or vapour can delay MLD-HC opening and cause slow delivery. The guide calls for an initial line-integrity check, air removal and a functional test using a simulated 3 gph leak at 10 psi. Testing is required at startup and periodically thereafter; the factory guide specifies at least annually. The PDF shows the test apparatus and sequence.

High-capacity pump in an installation

The 6″ riser supports the pump on the tank, with motor and hydraulics submerged and delivery lines connected to the upper manifold. The drawing locates the manifold, PMA, electrical conduit and intake. Its extractable design supports servicing without dismantling all delivery piping. Final length depends on tank depth and burial geometry.

Full installation manuals and drawings

Consult the specific model’s factory manual for the complete installation/service sequence, connections and safety requirements.

High-flow mechanical detection

MLD-HC serves high-capacity fuel lines. Its piston minimizes flow restriction, and a 94.22 cm³ chamber helps reduce nuisance trips caused by cold-weather contraction. STP-MLD-HC is the gasoline execution and STP-MLD-HCD the diesel execution. Detection is rated 3 gph (11.4 L/h) at 10 psi (0.69 bar).

Dimensions and installation clearance

Dimensions are 197 × 381 mm and weight 12.7 kg. It remains open at 0.14 bar dynamic outlet pressure; allowable static head to the dispensing point is 3.7 m. Top clearance from the 3″ NPT port centreline is 241 mm, reduced to 76.2 mm with horizontal installation. O-ring sealing simplifies fitting and removal.

Factory photos and details

Select an image to enlarge

High-flow mechanical detection
MLD-HC adapter and tank return
High-capacity pump in an installation

Descriptions include series-wide and optional features. Check the selected model’s table and documents for its actual configuration.

Original description and contents — 401315902

Manufacturer data (English)

High Capacity Line Leak Detectors

Model Number401315902
DescriptionSTP-MLD-HC leak detector complete with Adapter "T" (for gasoline)
Series data and documents — Manufacturer data (English)

Detects leaks of 3 gph (11.4 lph) or greater at 10 psi (0.69 bar).

Third party evaluated to comply with US EPA requirements 280.41 (B) and 280.44 (A) for continuous monitoring of pressurized piping.

Size: 7¾" × 15" (197 mm x 381 mm).

Weight: 28 pounds (12.7 kg).

The MLD-HC will remain in the open flow position with dynamic line pressure at 0.14 bar at the outlet.

Maximum static head pressure without affecting operation is 12' (3.7 m) from MLD-HC to dispensing point.

Minimum height required from 3" (76.2 mm) NPT port centerline for top clearance is 9½" (241 mm). Not position sensitive. Can be installed horizontally to reduce clearance to 3" (76.2 mm).

Compatible with all blends of motor fuels including alcohol blends from 0 to 10% ethanol, 20% MTBE or ETBE with 80% gasoline, or 17% TAME with 83% gasoline as well as diesel, fuel oil, Avgas, jet fuel or kerosene.

Two models available: STP-MLD-HC for gasoline, STP-MLD-HCD for diesel.

Consult factory for applicable approvals.

Franklin Fueling Systems is an ISO 9001 Certified Manufacturer.

High Capacity Line Leak Detectors

Model NumberDescription
401315902STP-MLD-HC leak detector complete with Adapter "T" (for gasoline)
401320902STP-MLD-HCD leak detector complete with Adapter "T" (for diesel)
401315901Replacement high capacity leak detector ONLY (for gasoline)
401325901Replacement Adapter “T" with cover assembly
401316930Replacement cover assembly
401320901Replacement high capacity leak detector ONLY (for diesel)
400449902MLD-HC hardware pack, includes fittings and documentation
Source page ↗ Franklin Electric Fueling Systems

About this product

Description

FE PETRO MLD-HC is a mechanical detector for high-capacity fuel lines. Under the specified conditions it detects leaks of 3 gph (11.4 L/h) or greater at 10 psi. Gasoline and diesel versions include complete T-adapter kits and detector-only replacements.