FE PETRO MLD+ — mechanical fuel leak detector – series illustration

Series illustration

FE PETRO MLD+ — mechanical fuel leak detector

FE PETRO MLD+ monitors leaks in pressurized fuel piping and restricts delivery when a leak is detected. Correctly installed with the appropriate fuel, it detects 3 gph (11. Read more →

Model code (SKU)PN-FF-403168901
Model
403168901
Factory order code
403168901
brands
FE PETRO / Franklin Electric
Leak detection
3 gph / 11.4 L/h @ 10 psi
Model designation
STP-MLD+G

Price

on request

Send an inquiry to receive prices and delivery terms within 1–2 days.

Send an inquiryContact us
  • Official dealer for 20+ brands
  • Delivery in Georgia
  • 20+ years of experience

Select a model by clicking its data in the table.

Compare models

Model

Construction, operation and model selection

Detailed description and use

System application and installation

Installed, grouped and component views

Vent connection to the tank
MLD and coordinated multiple-pump control
Air removal and leak testing

What the MLD+ monitors

MLD+ tests the downstream fuel line up to the dispenser solenoid. It does not monitor tank-wall leakage or pump sections upstream of the detector, so it is placed close to the pump. The manual describes systems operating at 20–50 psi pump pressure. Gasoline and diesel executions must match their permitted blends.

Vent connection to the tank

The vent tube above the MLD+ installed in its 2″ NPT socket connects to the manifold’s TANK port. It returns air displaced by the piston and any drained liquid to the tank. The tube must remain unkinked and drain freely. The manual distinguishes TANK from SYPHON: the detector vent must not connect to the syphon port.

Air removal and leak testing

Trapped air or vapour can delay MLD+ opening and cause slow delivery. The guide calls for an initial line-integrity check, air removal and a functional test using a simulated 3 gph leak at 10 psi. Testing is required at startup and periodically thereafter; the factory guide specifies at least annually. The PDF shows the test apparatus and sequence.

MLD and coordinated multiple-pump control

TB013 requires only one lead pump during an MLD test. Two independently running detectors can yield an approximately 6 gph combined threshold instead of preserving the individual 3 gph protection. The document names suitable alternating/primary-secondary modes for STP-SCI/SCIII, MagVFC, SPGC-220 and TPGC-380. The drawing is not automatically applicable to other models.

Pressure and reverse flow in grouped systems

TB013 specifies suitable STD check valves with approximately 40 psi factory relief settings. Additional series check valves must not obstruct pressure relief. With pumps exceeding 40 psi connected across separate tanks, fuel may transfer into another tank; the document calls for additional overfill-control measures for that case.

Full installation manuals and drawings

Consult the specific model’s factory manual for the complete installation/service sequence, connections and safety requirements.

Factory video guides

Syphon jet cleaning and replacement

Syphon jet cleaning and replacement

Watch video ↗
4″ pump check-valve replacement

4″ pump check-valve replacement

Watch video ↗
Controller fault codes

Controller fault codes

Watch video ↗
Submersible fuel-pump installation

Submersible fuel-pump installation

Watch video ↗
PMA pump-motor assembly replacement

PMA pump-motor assembly replacement

Watch video ↗
Pump lead assembly replacement

Pump lead assembly replacement

Watch video ↗
Electrical yoke replacement

Electrical yoke replacement

Watch video ↗

Purpose and operation

MLD+ monitors the pressurized fuel line between the submersible pump and dispenser. A piston and metering pin inside its compact housing test rigid, flexible or combined piping. A detected leak restricts delivery, giving the operator a noticeable indication.

Four versions for different fuels

MLD+G uses a blue cover and copper vent tube for gasoline up to E10. MLD+D uses a gold cover and copper tube for diesel up to B5. MLD+AG has a blue cover and stainless tube for gasoline up to E85. MLD+BD has a gold cover and stainless tube for B20 or B100 biodiesel.

Detection threshold and response

With correct installation and the specified fuel, detection is rated at 3 gph (11.4 L/h) at 10 psi (0.70 bar). A leak indication reduces delivery below 3 gpm (11.4 L/min) and takes over four seconds to open. The hourly leak threshold and restricted delivery per minute are different quantities.

Installation and operating limits

Install in the 2″ NPT detector port of a 4-inch STP or a separate adapter tee. It remains open during delivery down to 1 psi (0.07 bar), then resets for testing when pressure falls below 3 psi (0.21 bar) with the pump off. Detection extends up to 3 m above the installation point.

Piping capacity and compatibility

Published piping capacities are up to 165.1 US gal rigid, 109.8 US gal flexible and 274.9 US gal combined. Maximum viscosity is 70 SSU at 15°C. Use the specific version’s documentation for other fuel blends, MTBE/ETBE/TAME content and approvals; chemical compatibility differs between versions.

Factory photos and details

Select an image to enlarge

Purpose and operation
Vent connection to the tank
MLD and coordinated multiple-pump control
Air removal and leak testing

Descriptions include series-wide and optional features. Check the selected model’s table and documents for its actual configuration.

Original description and contents — 403168901

Manufacturer data (English)

Standard Fuel MLD+ Mechanical Leak Detectors

Model Number403168901
DescriptionSTP-MLD+G for gas, single pack (blue cover, copper vent tube, brass fittings)
Series data and documents — Manufacturer data (English)

All models are capable of detecting line leaks equivalent to 3 gph at 10 psi (11.4 lph @ 0.70 bar) when installed properly with the appropriate fuels - all models will signal detection of leaks by restricting product delivery to less than 3 gpm (11.4 lpm) and taking more than 4 seconds to open

All models will remain in the open position during product delivery to manifold, with discharge pressures as low as 1 psi (0.07 bar) - all models will reset to "tripped" when line pressure delay is below 3 psi (0.21 bar) with pump off

Detects leaks up to 10 feet (3 meters) above the point of installation

Max. liquid viscosity of 70 SSU at 60 °F (15 °C)

Gasoline models (blue cover, MLD+G and MLD+AG) are also listed for fuel mixtures containing 20% MTBE, 20% ETBE or 17% TAME with gasoline as well as diesel fuels, fuel oils, kerosene, Avgas and jet fuels.

Diesel models (gold cover, MLD+D and MLD+BD) are also listed for kerosene applications

cULus listed.

Third party certified to comply with US EPA requirements 280.41 (B) and 280.44 (A) for continuous monitoring of pressurized piping.

Consult factory for other applicable approvals.

Standard Fuel MLD+ Mechanical Leak Detectors

Model NumberDescription
403168901STP-MLD+G for gas, single pack (blue cover, copper vent tube, brass fittings)
403168903STP-MLD+G for gas, three pack
403170901STP-MLD+D for diesel, single pack (gold cover, copper vent tube, brass fittings)
403170903STP-MLD+D for diesel, three pack
403172903STP-MLD+D combo, three pack (contains two STP-MLD+G and one STP-MLD+D

Biofuel MLD+ Mechanical Leak Detectors

Model NumberDescription
403169901STP-MLD+AG for alcohol-gas, single pack (blue cover, stainless steel tube and fittings)
403169903STP-MLD+AG for alcohol-gas, three pack
403171901STP-MLD+BD for biodiesel, single pack (gold cover, stainless steel tube and fittings)
403171903STP-MLD+BD for biodiesel, three pack

MLD+ Mechanical Leak Detector Repair Parts & Accessories

Model NumberDescription
400440101Vent tube (for use with MLD+G and MLD+D)
400449903Hardware pack (fittings and documentation for MLD+G and MLD+D)
400449904Hardware pack (fittings and documentation for MLD+AG and MLD+BD)
400518001Leak detector Adapter tee
403123001Vent tube, stainless steel (for use with MLD+AG and MLD+BD)
Source page ↗ Franklin Electric Fueling Systems